V5001PF Flanged Kombi Auto

The V5001P Kombi-Auto ‘flanged’ differential pressure control valve is used to automatically maintain a hydronic balance in residential or commercial heating and cooling systems, installed in the return pipeline. Used in systems with variable volume flows maintaining differential pressure at a constant set level even under changing flow or pump pressure conditions.

  • Cast Iron body
  • High flow rates
  • System Pressure rating PN16
  • Water / water glycol mix (max 50%) to VDI 2035 -20°C to 130°C
  • Composite construction valve insert with PTFE seat seal
  • Sizes: 65mm to 100mm with flanged connections to EN 1092-2
  • SafeconTM quick measuring connections
  • Impulse tube included

 

Part NumberDN SizeKvs ValuePressure RangeFlow Range L/h
V5001PF1065 65 52 20-100kPa 600-49000
V5001PF1080 80 75 20-100kPa 600-70000
V5001PF1100 100 96 100kPa 1100-90000
V5001PF2065 65 52 40-200kPa 750-75000
V5001PF2080 80 75 40-200kPa 750-95000
V5001PF2100 100 96 40-200kPa 2000-136000