Designed for use in variable and constant flow systems, PICVs may be used, without an actuator, as constant flow limiter in constant flow systems or, with an actuator and temperature control connected, as a Pressure Independent Control Valve in variable flow systems.



PICVs are typically used for balancing and temperature control of fan coil units, air handling units, chilled ceilings and one-pipe heating systems

Linear PICV Valve Stroke 2.7 mm Actuator Optional 15mm to 25mm Flow rates 45 l/h to 1500 l/h Kvs 150 to 1500 Dezincification resistant (DZR) brass body High flow rates / wide Differential Pressure range System Pressure rating PN25 Water / water glycol mix (max 50%) to VDI 2035  -10°C to 120°C...
Linear PICV Valve Stroke 6.0 mm Actuator Optional 20mm to 32mm Flow rates 220 l/h to 3000 l/h Kvs 2200 to 3000 Dezincification resistant (DZR) brass body High flow rates / wide Differential Pressure range System Pressure rating PN25 Water / water glycol mix (max 50%) to VDI 2035  -10°C to...
Rotary PICV Valve Actuator Optional 32mm to 65mm Flow rates 1800 l/h to 18000 l/h Kvs 6000 to 18000 Ductile Iron body High flow rates / wide Differential Pressure range System Pressure rating PN16 Water / water glycol mix (max 50%) to VDI 2035  -10°C to 120°C Sizes: 32mm to 65mm with screwed...
Rotary PICV Valve with Actuator included 50mm to 150mm Flow rates 2000 l/h to 100000 l/h Kvs 20000 to 150000 Ductile Iron body High flow rates / wide Differential Pressure range System Pressure rating PN16 Water / water glycol mix (max 50%) to VDI 2035  -10°C to 120°C Sizes: 50mm to 150mm...
A range of compatible Honeywell Actuators are available for use with the V5004 Kombi-QM PICV MT4 / MT8 / M4410 Thermoelectric Actuators The V5001P Kombi-Auto  ‘screwed’ differential pressure control valve is used to automatically maintain a hydronic balance in residential or commercial heating and...
BIM DOWNLOADS
Get the latest Honeywell Building Information Modelling (BIM) files now.